:0086-577-62925511

:116@cnheli.com

back

The current position:HOME > PRODUCT > Rotary air damper actuator >

HLF02-08DN rotary non-spring return air damper actuator

Damper actuator 

  

Model

HLF02
 04D

HLF02
 08D

HLF02
 16D

HLF02
 24D

HLF02
 32D

HLF02
 04A

HLF02
 08A

HLF02
 16A

HLF02
 24A

Output Torque

4Nm

8Nm

16Nm

24Nm

32Nm

4Nm

8Nm

16Nm

24Nm

Max Baffle Plate size

1m

2m

4m

6m

6m

1m

2m

4m

6m

Time for Rotating 90°

35S

30S

80S

125S

140S

35S

30S

80S

125S

Modulating Scope

                           0~90° (In 5°Incerments)

Operating Voltage

24VAC/24VDC      AC220V~230V  50/60Hz       AC110V  50/60Hz

Power Rating

4W

3.9W/4.8W

4W

2.5W

             4W/4.8W

Control Input

2/3( Flocating Points)

 0~10VDC              4~20mA

Position Output


0~10VDC            4~20mA

Driving Shafts

8~32Nm Cylinder shaft size: φ20mm; Square shaft size: 16x16mm

4Nm Cylinder shaft size: φ16mm; Square shaft size: 12x12mm

Housing

                    ABS engineering plastic

Ambient Temperature

        Operation:-20~+50°C          Storage:-40~+80°C

Relative Humidity

                           0~90%RH

Protection

                             IP54

Noise Grade

                           45Db (A)

Net Weight

                  8~32Nm: 1.1kg        4Nm :0.7kg

Certificate

                          CE,  ISO9001

Usage life

                             60,000

  • Easy installation:
    • Fix the actuator to the damper shaft by universal grip
    • Various fixing support of special actuator (refer to the photo of the standard configuration of installation support) will be supplied according to the customers' requirements
    • By adjusting the pot, the rotation angle of the actuator can be adjusted and the matching of working range and feedback signal will be completed automatically
  • Convenient function checking:
    • The testing for the function of damper operation is convenient as well by pressing the manual button of the actuator, the actuator will escape from the gearing
    • User can operate the damper manually by pressing the manual button without releasing operation without power is forbidden
    • Good and reliable performance
    • With the function of overload protecting, actuator adopts dual-rotation hysteresis Synchronous motor, unnecessary with limitation switch, the actuator will stop by clutching the actuator when running to the end

The actuator has the mechanical limitation position of adjustable precision, timing pot